FlowMax · Combi boiler
H2O Low water pressure in heating circuit
What the control is telling you
The water pressure switch has opened because heating system pressure is too low; the unit stops at 0.3 bar (4.3 psi). Normal fill pressure is 1 bar (14.5 psi), around 1.2 bar mid-green on the gauge. The 120 troubleshooting table prints it as 'H20'.
Applies to: FLOWMAX-90, FLOWMAX-120
Likely causes
- Low system pressure (leak, air vented off, never filled)
- Water pressure switch wire disconnected
- Water pressure switch faulty
Test and repair steps
- Read the pressure gauge on the bottom of the unit; it should not be below 1 bar (14.5 psi).
- If low, open the fill tap and bring the system to about 1 to 1.2 bar, watching that H2O clears, then close the fill tap. The unit restarts on its own.
- If pressure keeps dropping, look for leaks in the system, the relief valve discharging, or a failed expansion tank.
- If pressure is correct but H2O stays on, check the pressure switch wiring.
- If wiring is good, replace the water pressure switch.
Settings for these units
Installation clearances · FlowMax condensing combi (FLOWMAX-90/120)
| Location | Service clearance (in) | To combustibles |
|---|---|---|
| X (side) | 0 | 0 in |
| Y (side) | 0 | 0 in |
| L | 16 | - |
| H | 24 | - |
| A (above) | 12 | 0 in from jacket top |
| B (below) | 12 | - |
| Front | - | 0 in |
| Rear | - | 0 in |
Wall-mount on a flat, solid vertical wall that can carry the weight.
Letters follow fig. 1 of the manual; L and H are the clearance zone in front/around the unit as drawn.
Hot water scald risk by temperature · FlowMax condensing combi (FLOWMAX-90/120)
| Temperature setting | Time to 2nd/3rd degree burn (adult skin) |
|---|---|
| Over 170°F | Nearly instantaneous |
| 160°F | About 1/2 second |
| 150°F | About 1-1/2 seconds |
| 140°F | Less than 5 seconds |
| 130°F | About 30 seconds |
| 120°F or less | More than 5 minutes |
120°F lowers scald risk; children, elderly and disabled people burn faster.
Fit a tempering (mixing) valve if water is stored or set hotter, e.g. with parameter 1 = 03 (up to 160°F).
Models that show this code
2 models in FlowMax condensing combi (FLOWMAX-90/120)
Other codes on the same units
- E12 DHW storage tank (cylinder) sensor fault
- E14 Air pressure switch tripped
- E16 Fan (blower) fault
- E22 Parameter programming request
- E35 Flame detection fault (false flame)
- E42 Fan speed control board fault
- Outdoor temp Outdoor temperature readout
- Summer mode symbol Summer mode selected (hot water only)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: FlowMax FLOWMAX-120 Instruction Manual, 6.10 Troubleshooting table, p.66; FlowMax FLOWMAX-120 Instruction Manual, 6.11 Diagnostics error code list, p.67; FlowMax FLOWMAX-90 User Manual, Diagnostics - Error codes, p.8-9. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.