FlowMax · Combi boiler
E35 Flame detection fault (false flame)
What the control is telling you
The board is detecting a flame signal when it should not, or the flame circuit is faulty.
Applies to: FLOWMAX-90, FLOWMAX-120
Likely causes
- Ionization electrode faulty or dirty
- Ionization electrode lead faulty
- Control board faulty
Test and repair steps
- Turn off power and gas before removing the electrode.
- Inspect the ionization electrode; clean it, or replace it if damaged.
- Check the ionization lead and replace it if faulty.
- If the code remains, replace the control board.
- Warning: Gas work only by a qualified gas technician; leak-test all gas connections after any repair.
Settings for these units
- Installation clearances · FlowMax condensing combi (FLOWMAX-90/120)
- Hot water scald risk by temperature · FlowMax condensing combi (FLOWMAX-90/120)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: FlowMax FLOWMAX-120 Instruction Manual, 6.10 Troubleshooting table, p.66; FlowMax FLOWMAX-120 Instruction Manual, 6.11 Diagnostics error code list, p.67; FlowMax FLOWMAX-90 User Manual, Diagnostics - Error codes, p.8-9. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.