Daikin · Heat pump

E57 Sweating on the cooling loop (3.5 to 5.0 ton only)

Medium severity DX6VSDZ6VS

What the control is telling you

The control senses sweating on the cooling loop. This code may not show on the thermostat, so check the outdoor unit error history.

Applies to: DX6VS/DZ6VS outdoor unit, 3.5 to 5.0 ton

Likely causes

  • Refrigerant leak
  • Low refrigerant charge
  • Faulty indoor EEV or indoor EEV coil
  • Thermistors inoperable or poorly connected

Test and repair steps

  1. Run the leak test procedure.
  2. Check refrigerant charge and adjust if needed.
  3. Check the indoor EEV. Replace if needed.
  4. Check the indoor EEV coil. Replace if needed.
  5. Check the connection to the thermistors. Repair or replace if needed.

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: SiUS612209EA service instructions, p. 47. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.