Daikin · Heat pump
Green LED: Off Green receive LED off
What the control is telling you
Either there is no power to the unit or there is a communication error.
Applies to: DX6VS/DZ6VS outdoor unit (H2P) and indoor unit (H3P)
Likely causes
- No power to unit
- Open fuse
- Communication error
Test and repair steps
- Check circuit breakers and fuses and reset or replace if needed.
- Reset the network by pressing the learn button.
- Check communication wires (terminal 1 and terminal 2) and replace if needed.
- Check for shorts in the low voltage wiring.
Other codes on the same units
- E57 Sweating on the cooling loop (3.5 to 5.0 ton only)
- Green LED: 1 steady flash Green LED steady flash, no network found
- Green LED: Rapid flashing Green LED rapid flashing, normal network traffic
- Green LED: Solid on Green LED solid, terminal 1 / terminal 2 miswire
- Red LED: 1 flash Red LED 1 flash, communications failure
- Red LED: 2 flash Red LED 2 flash, out-of-box reset
- Red LED: Off Red communications LED off
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin DX6VS/DZ6VS outdoor unit installation manual, p. 47. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.