Daikin · Heat pump

Green LED: Solid on Green LED solid, terminal 1 / terminal 2 miswire

High severity DX6VSDZ6VS

What the control is telling you

Terminal 1 and terminal 2 are reversed, shorted, or shorted to terminal C or R.

Applies to: DX6VS/DZ6VS outdoor unit and indoor unit control boards

Likely causes

  • Terminal 1 and terminal 2 wires reversed at indoor unit, thermostat, or outdoor unit
  • Short between terminal 1 and terminal 2
  • Short between terminal 1 or 2 and terminal C (24VAC) or terminal R (24VAC, COM)

Test and repair steps

  1. Check communication wires (terminal 1 and terminal 2) and replace if needed.
  2. Check for reversed or shorted low voltage wiring.

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin DX6VS/DZ6VS outdoor unit installation manual, p. 47. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.