Daikin · Heat pump
E58 Compressor overload (OL) sensor open
What the control is telling you
Thermostat shows 58, outdoor board display shows E58. The compressor overload protection sensor is open.
Applies to: DH6VS***1*A*, DH7VSA[24-48]10A* (FIT and Enhanced Capacity/High Efficiency FIT)
Likely causes
- OL sensor not working
- Jumper wire X33A in the wrong spot or missing
Test and repair steps
- Kill power at the disconnect before opening the control box or touching wiring.
- Measure the OL sensor resistance. Replace it if bad.
- Check that the OL sensor sits right on the compressor body.
- Check jumper wire X33A is in place.
Models that show this code
11 models in Daikin FIT DH6VS/DH7VSA
Other codes on the same units
- E49 Charging mode blocked by indoor heat
- E50 Voltage problem on the control board
- E51 Communication problem seen by the outdoor board
- E56 Suction temperature sensor out of range
- Eb0 Indoor airflow near zero
- Eb9 Indoor airflow below what is needed
- Ed0 No shared data on the control
- Ed1 Bad shared or network data
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin 3P761829-1B FIT outdoor unit DC6VS/DH6VS/DC9VSA/DH7VSA installation & service reference, Troubleshooting table p.46 (printed page). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.