Carrier · Mini-split
EL 0C System lacks refrigerant
What the control is telling you
The control judges the refrigerant system from the number of compressor stops and from parameter changes caused by high exhaust temperature.
Applies to: D5FCFAH console ductless system, sizes 18K to 60K
Likely causes
- Refrigerant leak
- Refrigerant charge too low
- Loose T2 sensor
- T1 sensor too close to the evaporator
- Faulty indoor PCB
Test and repair steps
- Power off, then restart the unit 15 minutes later.
- Check for leaks and check the connections.
- Put your hand in front of the indoor air outlet. If no cool or warm air blows out, check the system.
- If T2 is loose, install it correctly.
- If T1 is too close to the evaporator, reposition it.
- If a leak is found, repair it and recharge the refrigerant.
- Charge the refrigerant appropriately (about 10 % of the nameplate charge).
- If the fault remains, replace the indoor PCB.
Models that show this code
11 models in D5FCFA
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier D5FCFAH service manual, p. 40. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.