Carrier · Mini-split

PC 03 High or low pressure protection

High severity D5FCFA

What the control is telling you

The outdoor pressure switch shuts the system off when high pressure is above 4.4 MPa or low pressure is below 0.13 MPa. The LED shows the failure code.

Applies to: D5FCFAH console ductless system, sizes 18K to 60K

Likely causes

  • Faulty high or low pressure switch wiring to the main board
  • Faulty high or low pressure protector
  • Outdoor ambient above 50 °C
  • Dirty outdoor heat exchanger
  • Outdoor fan not running properly or blocked ventilation
  • Low refrigerant charge
  • High pressure valve not fully open
  • Indoor fan not running properly in cooling mode

Test and repair steps

  1. High pressure check that the high pressure switch and main control board are wired correctly.
  2. High pressure disconnect the plug and measure the resistance of the high pressure protector. A normal protector reads 0.
  3. High pressure if the protector is broken, replace it.
  4. High pressure if the outdoor ambient is above 50 °C, check that the outdoor unit ventilation is good.
  5. High pressure clean the heat exchanger if it is dirty.
  6. High pressure check that the outdoor fan is running properly. If not, refer to the fan speed solution.
  7. High pressure if the problem remains, replace the outdoor main board.
  8. Low pressure check that the low pressure protector and main control board are wired properly. Reconnect them if needed.
  9. Low pressure disconnect the plug and measure the resistance of the low pressure protector. A normal protector reads 0. Replace it if broken.
  10. Low pressure if the outdoor ambient is too low, stop the unit and wait for conditions to rise.
  11. Low pressure fully open the valve core of the high pressure valve.
  12. Low pressure check that the indoor fan runs properly in cooling mode. If the fan speed is out of control, refer to that solution.
  13. Low pressure check the refrigerant system. If the charge is low, add refrigerant and see whether the system then runs properly.
  14. Replace the outdoor main board if the problem is not resolved.

Models that show this code

11 models in D5FCFA

D5FCFAH18XAKD5FCFAH24XAKD5FCFAH36XAKD5FCFAH48XAKD5FCFAH58XAKD5FCFH18XAKD5FCFH24XAKD5FCFH36XAKD5FCFH48XAKD5FCFH58XAKD5SCHA

Other codes on the same units

  • EH 0E Water-level alarm malfunction
  • EL 0C System lacks refrigerant
  • PC 01 Outdoor voltage protection
  • PC 04 Inverter compressor drive error
  • PC 0L Low ambient temperature protection

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier D5FCFAH service manual, p. 45-46. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.