Carrier · Mini-split

EH 0E Water-level alarm malfunction

Medium severity D5FCFA

What the control is telling you

If the sampling voltage is not 5 V, the LED shows this failure code.

Applies to: D5FCFAH console ductless system, sizes 18K to 60K

Likely causes

  • Water-level switch not inserted properly
  • Water-level switch broken
  • Water pump faulty
  • Indoor PCB faulty

Test and repair steps

  1. Shut off the power supply and turn it on again 2 minutes later.
  2. Check that the water-level switch is inserted properly. Reseat it if not.
  3. If the switch is broken, replace the water-level switch.
  4. If the fault remains, replace the water pump.
  5. If the fault still remains, replace the indoor main PCB.

Models that show this code

11 models in D5FCFA

D5FCFAH18XAKD5FCFAH24XAKD5FCFAH36XAKD5FCFAH48XAKD5FCFAH58XAKD5FCFH18XAKD5FCFH24XAKD5FCFH36XAKD5FCFH48XAKD5FCFH58XAKD5SCHA

Other codes on the same units

  • EL 0C System lacks refrigerant
  • PC 01 Outdoor voltage protection
  • PC 03 High or low pressure protection
  • PC 04 Inverter compressor drive error
  • PC 0L Low ambient temperature protection

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier D5FCFAH service manual, p. 41. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.