Carrier · Mini-split
EH 0b Indoor main board and display board communication error
What the control is telling you
The indoor PCB does not receive feedback from the display board.
Applies to: D5FSFAH
Likely causes
- Communication wire fault
- Display board fault
- Indoor PCB fault
Test and repair steps
- Check the wiring and connections.
- Ensure a proper connection if any are loose.
- Power off, then restart the unit 2 minutes later.
- If the error still shows, replace the display board.
- If the error still exists, replace the indoor main PCB.
Models that show this code
3 models in D5FSFA
Other codes on the same units
- EH 06 Indoor PCB and display board communication error
- EH 3A External fan DC bus voltage too low
- EH 3b External fan DC bus voltage too high
- EH 62 Indoor temperature sensor open or shorted
- EH 65 Indoor temperature sensor open or shorted
- EH 66 Indoor temperature sensor open or shorted
- EH C1 Refrigerant sensor detects leakage
- EH C2 Refrigerant sensor out of range and leakage detected
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier D5FSFAH service manual, p. 46. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.