Carrier · Mini-split

EH C1 Refrigerant sensor detects leakage

Critical severity D5FSFA

What the control is telling you

The sensor reads at least 10% of LFL for 10 s, or the multi-zone system receives a leakage protection fault from the outdoor unit. In multi-zone systems only the leaking indoor unit's buzzer sounds (10 s to 5 min). Other indoor units show the code without sounding. Any key on the remote, wired controller or app silences the alarm.

Applies to: D5FSFAH

Likely causes

  • Refrigerant leak
  • Refrigerant sensor reading high concentration

Test and repair steps

  1. Check the system for leaks.
  2. If a leak is found, repair it and recharge the refrigerant.
  3. If no leak is found, check the system for blockages and clear any found.
  4. If the problem remains, check the system for leaks again.

Models that show this code

3 models in D5FSFA

D5FSFAH09XAKD5FSFAH12XAKD5FSFAH16XAK

Other codes on the same units

  • EH 0b Indoor main board and display board communication error
  • EH 3A External fan DC bus voltage too low
  • EH 3b External fan DC bus voltage too high
  • EH 62 Indoor temperature sensor open or shorted
  • EH 65 Indoor temperature sensor open or shorted
  • EH 66 Indoor temperature sensor open or shorted
  • EH C2 Refrigerant sensor out of range and leakage detected
  • EH C3 Refrigerant sensor out of range

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier D5FSFAH service manual, p. 45. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.