Carrier · Mini-split

EH 66 Indoor temperature sensor open or shorted

Medium severity D5FSFA

What the control is telling you

The sampling voltage is below 0.06 V or above 4.94 V, so the sensor reading is invalid.

Applies to: D5FSFAH indoor unit

Likely causes

  • Open or shorted sensor
  • Loose or damaged sensor wiring
  • Faulty indoor PCB

Test and repair steps

  1. Check the connection between the sensor and the PCB.
  2. Measure the sensor resistance and compare it with the Appendix values on page 59.
  3. Replace the sensor if its resistance is out of range.
  4. If wiring and sensor are good, replace the indoor PCB.

Models that show this code

3 models in D5FSFA

D5FSFAH09XAKD5FSFAH12XAKD5FSFAH16XAK

Other codes on the same units

  • EH 0b Indoor main board and display board communication error
  • EH 3A External fan DC bus voltage too low
  • EH 3b External fan DC bus voltage too high
  • EH 62 Indoor temperature sensor open or shorted
  • EH 65 Indoor temperature sensor open or shorted
  • EH C1 Refrigerant sensor detects leakage
  • EH C2 Refrigerant sensor out of range and leakage detected
  • EH C3 Refrigerant sensor out of range

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier D5FSFAH service manual, p. 30. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.