Carrier · Mini-split

PC 04 Inverter compressor drive error

High severity D5FCFA

What the control is telling you

An abnormal inverter compressor drive is detected by a detection circuit that monitors communication signals, voltage, and compressor rotation speed signals.

Applies to: D5FCFAH console ductless system, sizes 18K to 60K

Likely causes

  • Improper wiring between PCB and compressor
  • Faulty IPM module board
  • Outdoor fan or poor outdoor ventilation
  • Faulty compressor
  • Faulty outdoor PCB

Test and repair steps

  1. Check the wiring between the PCB and the compressor. Correct any improper wiring or replace the wires and connectors.
  2. Check the IPM. If it is not functioning properly, replace the IPM board or the outdoor PCB.
  3. Check the outdoor fan and the outdoor unit ventilation. If the fan is not functioning properly, refer to the fan speed malfunction solution.
  4. Check the compressor resistance values. If they are outside acceptable parameters, replace the compressor.
  5. If the compressor is acceptable, replace the outdoor PCB.

Models that show this code

11 models in D5FCFA

D5FCFAH18XAKD5FCFAH24XAKD5FCFAH36XAKD5FCFAH48XAKD5FCFAH58XAKD5FCFH18XAKD5FCFH24XAKD5FCFH36XAKD5FCFH48XAKD5FCFH58XAKD5SCHA

Other codes on the same units

  • EH 0E Water-level alarm malfunction
  • EL 0C System lacks refrigerant
  • PC 01 Outdoor voltage protection
  • PC 03 High or low pressure protection
  • PC 0L Low ambient temperature protection

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier D5FCFAH service manual, p. 44. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.