Carrier · Mini-split
PC 01 Outdoor voltage protection
What the control is telling you
Abnormal increases or decreases in voltage are detected by the voltage detection circuit.
Applies to: D5FCFAH console ductless system, sizes 18K to 60K
Likely causes
- Faulty power supply
- Faulty connections or wires
- Faulty IPM module board
- Faulty reactor
- Faulty outdoor PCB
Test and repair steps
- Check the power supply. If it is not in working order, turn off the unit.
- Check the connections and wires. Ensure proper connections or replace the wires.
- With the unit in standby, measure the voltage between P and N. It should be around DC 310 V, 340 V or 380 V. On startup it should be 220 V to 400 V.
- If the voltage is wrong, replace the IPM board.
- Check the reactor. If it is not working, replace the reactor.
- If the reactor is working, replace the outdoor PCB.
- Skip the cover-related step for models whose electric control box cover cannot be removed. See the disassembly guide.
Models that show this code
11 models in D5FCFA
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier D5FCFAH service manual, p. 43. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.