EL 01 Indoor and outdoor unit communication error

Medium severity D5FSCAHD5FLCAH

What the control is telling you

The indoor unit cannot communicate with the outdoor unit over the current loop (S communication).

Applies to: Indoor and outdoor units, all sizes

Likely causes

  • Loose or wrong wiring between indoor and outdoor units
  • Faulty indoor or outdoor PCB
  • Faulty reactor
  • Shorted 4-way valve, heater or fan component
  • Faulty electronic expansion valve coil
  • Faulty IPM board

Test and repair steps

  1. Power off, then restart the unit after 2 minutes. If the code clears, stop.
  2. Check the wiring between indoor and outdoor units, from the outdoor terminal to the outdoor PCB, and between PCBs if there is more than one.
  3. Check the wiring from the indoor terminal to the indoor PCB.
  4. Check that the power LED is on and that W and 1(L) are connected where the unit has a W wire.
  5. Measure DC voltage between outdoor port 2 (S or L2) and port 3 (N or S), red on 2 and black on 3. Normal operation alternates positive and negative. A fixed value near 0 or always positive points to a fault.
  6. Measure the reactor that is not connected to a capacitor. Resistance should be close to zero ohms; otherwise replace the reactor.
  7. Unplug the expansion valve and each high-voltage load (4-way valve, heater, AC fan) one at a time and check resistance for a short. Replace any shorted part or the expansion valve coil.
  8. Check the AC voltage from IPM board output L and N against power input, and check DC 5V and 12V to the main PCB. Replace the IPM board or main PCB if wrong.
  9. If the fault remains, replace the outdoor PCB.

Other codes on the same units

  • EH 00 EEPROM malfunction (indoor PCB)
  • EH 03 Fan speed out of control (indoor)
  • EH 0A EEPROM malfunction (indoor PCB)
  • EH 60 Temperature sensor open or short circuit (indoor)
  • EH 61 Temperature sensor open or short circuit (indoor)
  • EH b3 Communication fault between wired controller and indoor master control
  • EH bA Communication error between indoor unit and external fan module
  • EL 16 Error code EL 16

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: D5FSCAH / D5FLCAH service manual, p. 35-36. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.