Carrier · Mini-split
EH bA Communication error between indoor unit and external fan module
What the control is telling you
The indoor unit receives no feedback from the external fan module for 150 seconds, or it receives abnormal voltage changes from the module.
Applies to: D5FSCAH / D5FLCAH
Likely causes
- Fan module connection problem
- Indoor main PCB fault
Test and repair steps
- Check that ENC1 is connected correctly.
- Reset ENC1.
- If the code still shows, replace the indoor main PCB.
Other codes on the same units
- EH 00 EEPROM malfunction (indoor PCB)
- EH 03 Fan speed out of control (indoor)
- EH 0A EEPROM malfunction (indoor PCB)
- EH 60 Temperature sensor open or short circuit (indoor)
- EH 61 Temperature sensor open or short circuit (indoor)
- EH b3 Communication fault between wired controller and indoor master control
- EL 01 Indoor and outdoor unit communication error
- EL 16 Error code EL 16
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier D5FSCAH/D5FLCAH service manual, p. 50. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.