Carrier · Mini-split
EH 03 Fan speed out of control (indoor)
What the control is telling you
Indoor fan speed stays too low or too high for a set time. The unit stops and the LED shows the fault.
Applies to: Indoor fan
Likely causes
- Wiring fault
- Fan assembly or fan binding
- Faulty fan motor
- Faulty PCB
Test and repair steps
- Power off, then restart the unit after 2 minutes. If the fault stays, continue.
- Check that the wiring is correct and connections are proper.
- Shut off the power and turn the fan by hand. If it does not turn easily, find and clear the cause.
- Test the indoor DC fan motor voltages in standby (see fan motor test values, p. 39). If out of range, replace the PCB.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: D5FSCAH / D5FLCAH service manual, p. 38-39. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.