Carrier · Mini-split
EC 54 Temperature sensor open or short circuit
What the control is telling you
The sampling voltage is below 0.06 V or above 4.94 V, so the sensor circuit is open or shorted.
Applies to: Outdoor unit sensors
Likely causes
- Open or shorted sensor
- Wiring fault or poor connection
- Faulty PCB
Test and repair steps
- Check that the sensor is properly wired and connected.
- Check the sensor resistance against the values in the Appendix, p. 78.
- If the wiring is good and the fault remains, replace the outdoor PCB.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: D5FSCAH / D5FLCAH service manual, p. 40. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.