Carrier · Mini-split

EC 07 Fan speed out of control (outdoor)

Medium severity D5FSCAHD5FLCAH

What the control is telling you

Outdoor fan speed stays too low or too high for a set time. The unit stops and the LED shows the fault.

Applies to: Outdoor fan

Likely causes

  • Wiring fault
  • Fan assembly or fan binding
  • Faulty outdoor fan motor
  • Faulty outdoor PCB

Test and repair steps

  1. Power off, then restart the unit after 2 minutes. If the fault stays, continue.
  2. Check that the wiring is correct and connections are proper.
  3. Shut off the power and turn the fan by hand. If it does not turn easily, find and clear the cause.
  4. Release the UVW connector and measure resistance U-V, U-W and V-W. If they are not equal, replace the fan motor. If they are equal, replace the PCB.

Other codes on the same units

  • EC 51 EEPROM malfunction (outdoor PCB)
  • EC 52 Temperature sensor open or short circuit
  • EC 53 Temperature sensor open or short circuit
  • EC 54 Temperature sensor open or short circuit
  • EC 55 Error code EC 55
  • EC 56 Temperature sensor open or short circuit
  • EC 57 Error code EC 57
  • EC 5C Error code EC 5C

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: D5FSCAH / D5FLCAH service manual, p. 32, 38-39. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.