Carrier · Mini-split

EC 0d Outdoor unit malfunction detected by indoor unit

High severity D5FSFA

What the control is telling you

The indoor unit detects an error in the outdoor unit.

Applies to: D5FSFAH

Likely causes

  • Outdoor unit fault
  • Outdoor main board fault
  • Blockage or leak in the refrigerant system

Test and repair steps

  1. Power off, then restart the unit 2 minutes later.
  2. Check whether the outdoor main board shows an error a few minutes later.
  3. If it does, refer to the prescribed steps for that displayed error.

Models that show this code

3 models in D5FSFA

D5FSFAH09XAKD5FSFAH12XAKD5FSFAH16XAK

Other codes on the same units

  • EH 06 Indoor PCB and display board communication error
  • EH 0b Indoor main board and display board communication error
  • EH 3A External fan DC bus voltage too low
  • EH 3b External fan DC bus voltage too high
  • EH 62 Indoor temperature sensor open or shorted
  • EH 65 Indoor temperature sensor open or shorted
  • EH 66 Indoor temperature sensor open or shorted
  • EH C1 Refrigerant sensor detects leakage

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier D5FSFAH service manual, p. 45. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.