Carrier · Heat pump

PC 0L Low ambient temperature protection

Medium severity D5FUAA

What the control is telling you

Protection function. With the compressor off, the stop threshold is outdoor ambient (T4) below -35°C for 10 s. With the compressor on, it is T4 below -40°C for 10 s. The unit exits protection when T4 is at or above -32°C for 10 s.

Applies to: D5FUAA heat pump outdoor unit

Likely causes

  • Outdoor ambient temperature below the protection limit

Models that show this code

8 models in D5FUAA

37MUHA37MURAD5FUAAH18AAKD5FUAAH24AAKD5FUAAH30AAKD5FUAAH36AAKD5FUAAH48AAKD5FUAAH60AAK

Other codes on the same units

  • EH C3 Refrigerant sensor out of range
  • EH b3 Communication malfunction between wired controller and master control
  • EH bA Communication malfunction between indoor unit and external fan module
  • EL 01 Indoor and outdoor unit communication error
  • EL 0C System lacks refrigerant
  • EL 16 Communication malfunction between adapter board and outdoor main board
  • FH CC Refrigerant sensor error
  • FL 09 Mismatch between new and old platforms

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: D5FUAA service manual, p. 36. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.