EL 16 Communication malfunction between adapter board and outdoor main board
What the control is telling you
The adapter PCB cannot detect the outdoor main control board.
Applies to: D5FUAA outdoor unit with adapter board
Likely causes
- Faulty connection wires
- Faulty adapter board
- Faulty outdoor main PCB
Test and repair steps
- Power off, then restart the unit after 3 minutes.
- If the error remains, check the wiring and connections. Ensure proper connections.
- If the connections are good, replace the adapter main PCB.
- If the problem remains, replace the outdoor main control board.
Models that show this code
8 models in D5FUAA
Other codes on the same units
- EH C2 Refrigerant sensor out of range and leakage detected
- EH C3 Refrigerant sensor out of range
- EH b3 Communication malfunction between wired controller and master control
- EH bA Communication malfunction between indoor unit and external fan module
- EL 01 Indoor and outdoor unit communication error
- EL 0C System lacks refrigerant
- FH CC Refrigerant sensor error
- FL 09 Mismatch between new and old platforms
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: D5FUAA service manual, p. 40. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.