Carrier · Heat pump

EL 01 Indoor and outdoor unit communication error

Medium severity D5FUAA

What the control is telling you

The indoor unit cannot communicate with the outdoor unit.

Applies to: D5FUAA indoor and outdoor units

Likely causes

  • Signal wire loose or not seated on the PCB
  • Signal wire broken
  • Interference from nearby lamps or power transformers, or signal wire too long
  • Signal cable not shielded or shield not earthed
  • Faulty indoor or outdoor main PCB

Test and repair steps

  1. Power off, then restart the unit 2 minutes later.
  2. Check that the signal wires are inserted properly on the PCB; pull out and reinsert them.
  3. Check the signal wire for breaks and replace it if damaged.
  4. Check that the signal wire is shielded cable and that the shield is earthed.
  5. Look for interference sources and check the signal wire length; remove interference or add a magnetic ring on the power wire.
  6. If the error stays, replace the indoor main PCB.
  7. If the error still stays, replace the outdoor main PCB.

Models that show this code

8 models in D5FUAA

37MUHA37MURAD5FUAAH18AAKD5FUAAH24AAKD5FUAAH30AAKD5FUAAH36AAKD5FUAAH48AAKD5FUAAH60AAK

Other codes on the same units

  • EH C1 Refrigerant sensor detects leakage
  • EH C2 Refrigerant sensor out of range and leakage detected
  • EH C3 Refrigerant sensor out of range
  • EH b3 Communication malfunction between wired controller and master control
  • EH bA Communication malfunction between indoor unit and external fan module
  • EL 0C System lacks refrigerant
  • EL 16 Communication malfunction between adapter board and outdoor main board
  • FH CC Refrigerant sensor error

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: D5FUAA Service Manual, p. 24. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.