EH C1 Refrigerant sensor detects leakage

High severity D5FUAA

What the control is telling you

The refrigerant sensor reads 10% of LFL or higher for 10 seconds. In multi-zone systems, only the indoor unit that detects the leak sounds the buzzer, for 10 seconds up to 5 minutes; other indoor units show the code without sound. A key press on the remote, wired controller or app can silence the alarm.

Applies to: D5FUAA system with refrigerant sensor

Likely causes

  • Refrigerant leak in the system
  • Refrigerant concentration at the sensor above the threshold

Test and repair steps

  1. Check the system for leaks. If leaks are present, repair the leak and recharge the refrigerant.
  2. If no leak is found, check the system for blockages and clear any found.

Models that show this code

8 models in D5FUAA

37MUHA37MURAD5FUAAH18AAKD5FUAAH24AAKD5FUAAH30AAKD5FUAAH36AAKD5FUAAH48AAKD5FUAAH60AAK

Other codes on the same units

  • EH 61 Indoor temperature sensor open or short
  • EH 62 Indoor temperature sensor open or short
  • EH 65 Indoor temperature sensor open or short
  • EH 66 Indoor temperature sensor open or short
  • EH C2 Refrigerant sensor out of range and leakage detected
  • EH C3 Refrigerant sensor out of range
  • EH b3 Communication malfunction between wired controller and master control
  • EH bA Communication malfunction between indoor unit and external fan module

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: D5FUAA service manual, p. 38. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.