Carrier · Heat pump

EH 65 Indoor temperature sensor open or short

Medium severity D5FUAA

What the control is telling you

The sampling voltage is below 0.06 V or above 4.94 V and the display shows the failure.

Applies to: D5FUAA indoor unit

Likely causes

  • Sensor open or shorted
  • Sensor wiring or connection to the PCB faulty
  • Indoor PCB faulty

Test and repair steps

  1. Check the connection between the temperature sensor and the PCB.
  2. Measure the resistance of the sensor and compare with the Appendix table (page 53).
  3. If out of range, replace the sensor.
  4. If the wiring is faulty, ensure proper connections.
  5. If the sensor is good and the fault remains, replace the indoor PCB.

Models that show this code

8 models in D5FUAA

37MUHA37MURAD5FUAAH18AAKD5FUAAH24AAKD5FUAAH30AAKD5FUAAH36AAKD5FUAAH48AAKD5FUAAH60AAK

Other codes on the same units

  • EH 3b External fan DC bus voltage too high fault
  • EH 60 Indoor temperature sensor open or short
  • EH 61 Indoor temperature sensor open or short
  • EH 62 Indoor temperature sensor open or short
  • EH 66 Indoor temperature sensor open or short
  • EH C1 Refrigerant sensor detects leakage
  • EH C2 Refrigerant sensor out of range and leakage detected
  • EH C3 Refrigerant sensor out of range

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: D5FUAA Service Manual, p. 27. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.