Carrier · Heat pump
EH C3 Refrigerant sensor out of range
What the control is telling you
The indoor unit gets no feedback from the refrigerant sensor for 150 seconds, or the sensor reading is out of range.
Applies to: D5FUAA indoor unit with refrigerant sensor
Likely causes
- Loose or wrong connection between the refrigerant sensor and PCB
- Wrong ENC1 setting
- Faulty refrigerant sensor
- Faulty indoor main PCB
Test and repair steps
- Shut off the power and turn it on again 2 minutes later.
- If the code still shows, check that ENC1 is correct and reset ENC1 if needed.
- Check the connection between the refrigerant sensor and PCB. Ensure the connections are proper.
- If the wiring is good, replace the sensor.
- If the fault still exists, replace the indoor main PCB.
Models that show this code
8 models in D5FUAA
Other codes on the same units
- EH 62 Indoor temperature sensor open or short
- EH 65 Indoor temperature sensor open or short
- EH 66 Indoor temperature sensor open or short
- EH C1 Refrigerant sensor detects leakage
- EH C2 Refrigerant sensor out of range and leakage detected
- EH b3 Communication malfunction between wired controller and master control
- EH bA Communication malfunction between indoor unit and external fan module
- EL 01 Indoor and outdoor unit communication error
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: D5FUAA service manual, p. 37. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.