EH 62 Indoor temperature sensor open or short
What the control is telling you
The sampling voltage is below 0.06 V or above 4.94 V and the display shows the failure.
Applies to: D5FUAA indoor unit
Likely causes
- Sensor open or shorted
- Sensor wiring or connection to the PCB faulty
- Indoor PCB faulty
Test and repair steps
- Check the connection between the temperature sensor and the PCB.
- Measure the resistance of the sensor and compare with the Appendix table (page 53).
- If out of range, replace the sensor.
- If the wiring is faulty, ensure proper connections.
- If the sensor is good and the fault remains, replace the indoor PCB.
Models that show this code
8 models in D5FUAA
Other codes on the same units
- EH 3A External fan DC bus voltage too low protection
- EH 3b External fan DC bus voltage too high fault
- EH 60 Indoor temperature sensor open or short
- EH 61 Indoor temperature sensor open or short
- EH 65 Indoor temperature sensor open or short
- EH 66 Indoor temperature sensor open or short
- EH C1 Refrigerant sensor detects leakage
- EH C2 Refrigerant sensor out of range and leakage detected
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: D5FUAA Service Manual, p. 27. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.