Carrier · Heat pump
EL 0C System lacks refrigerant
What the control is telling you
The refrigerant system is judged low based on the number of compressor stops and changes in operating parameters caused by high exhaust temperature.
Applies to: D5FUAA system
Likely causes
- Refrigerant leak
- Refrigerant charge low
- T2 sensor loose
- T1 sensor too close to the evaporator
- Indoor PCB faulty
Test and repair steps
- Power off, then restart the unit 15 minutes later.
- Check whether cool or warm air comes out of the indoor air outlet.
- Check the system for leaks; repair any leak and recharge the refrigerant.
- Check that T2 is not loose.
- Check that T1 is not too close to the evaporator; install it correctly.
- Charge the refrigerant appropriately (about 10 % of the nameplate charge).
- If the fault remains, replace the indoor PCB.
Models that show this code
8 models in D5FUAA
Other codes on the same units
- EH C2 Refrigerant sensor out of range and leakage detected
- EH C3 Refrigerant sensor out of range
- EH b3 Communication malfunction between wired controller and master control
- EH bA Communication malfunction between indoor unit and external fan module
- EL 01 Indoor and outdoor unit communication error
- EL 16 Communication malfunction between adapter board and outdoor main board
- FH CC Refrigerant sensor error
- FL 09 Mismatch between new and old platforms
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: D5FUAA Service Manual, p. 28. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.