Carrier · Heat pump
EH 0b Indoor main control board and display board communication error
What the control is telling you
The indoor PCB does not receive feedback from the display board.
Applies to: D5FUAA indoor unit
Likely causes
- Faulty communication wire or connection
- Faulty indoor PCB
- Faulty display board
Test and repair steps
- Power off, then restart the unit 2 minutes later.
- Check the wiring and connections. Ensure proper connection.
- If the error remains, replace the indoor main PCB.
- If the error still exists, replace the display board.
Models that show this code
8 models in D5FUAA
Other codes on the same units
- EH 03 / EC 07 Fan speed outside normal range
- EH 3A External fan DC bus voltage too low protection
- EH 3b External fan DC bus voltage too high fault
- EH 60 Indoor temperature sensor open or short
- EH 61 Indoor temperature sensor open or short
- EH 62 Indoor temperature sensor open or short
- EH 65 Indoor temperature sensor open or short
- EH 66 Indoor temperature sensor open or short
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: D5FUAA service manual, p. 39. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.