Carrier · Heat pump
EH 0E Water-level alarm malfunction
What the control is telling you
The water-level sampling voltage is not 5 V and the LED shows the failure code. Recommended parts: connection wires, water-level switch, water pump, indoor PCB.
Applies to: D5FUHA
Likely causes
- Water-level switch not inserted properly
- Faulty water-level switch
- Faulty water pump
- Faulty indoor PCB
Test and repair steps
- Shut off the power supply and turn it on again 2 minutes later.
- Check that the water-level switch is inserted properly. If not, insert it properly.
- If the problem remains, check whether the water-level switch is broken. Replace it if it is.
- If the problem remains, replace the water pump.
- If the problem still remains, replace the indoor main PCB.
Other codes on the same units
- ---- Indoor units mode conflict
- DF Defrost mode
- EC 07 Outdoor fan speed operating outside normal range
- EC 55 Quick maintenance code (outdoor)
- EC 57 Quick maintenance code (outdoor)
- EC 5C Quick maintenance code (outdoor)
- EHbA Communication error between indoor unit and external fan module
- FC Forced cooling mode
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: D5FUHA service manual, p. 29. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.