Carrier · Heat pump
EH 0A EEPROM malfunction (indoor unit)
What the control is telling you
The indoor PCB main chip receives no feedback from its EEPROM chip.
Applies to: Indoor unit
Test and repair steps
- Turn the power off and wait 2 minutes before turning it back on.
- If the code still shows, replace the indoor main PCB.
Models that show this code
4 models in D5FCFA
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: D5FCFAH service manual, p. 33. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.