Carrier · Heat pump
EH 03 / EC 07 Fan speed outside normal range
What the control is telling you
The indoor or outdoor fan speed stays too low or too high for a set time. The display shows the code and the unit switches off.
Applies to: D5FUAA indoor and outdoor fans
Likely causes
- Fan assembly or fan motor faulty
- Fan wiring or connections faulty
- Main PCB faulty
Test and repair steps
- Shut off the power supply and turn the fan by hand; it should turn easily.
- Check that the fan is properly wired and that connections are secure.
- For indoor DC fan motor, check the voltages at the fan motor connector (see fan motor pin voltage table).
- If the problem remains, replace the main PCB.
Models that show this code
8 models in D5FUAA
Other codes on the same units
- EC 53 Outdoor temperature sensor open or short
- EC 54 Outdoor temperature sensor open or short
- EC 56 Outdoor temperature sensor open or short
- EH 0b Indoor main control board and display board communication error
- EH 3A External fan DC bus voltage too low protection
- EH 3b External fan DC bus voltage too high fault
- EH 60 Indoor temperature sensor open or short
- EH 61 Indoor temperature sensor open or short
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: D5FUAA Service Manual, p. 25. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.