Carrier · Heat pump
EH 03 Indoor fan speed outside normal range
What the control is telling you
The indoor fan speed stays too low or too high for a set time. The LED shows the code and the unit turns off.
Applies to: Indoor fan
Likely causes
- Fan blocked or hard to turn
- Poor wiring or connections
- Faulty fan motor or fan assembly
- Faulty PCB
Test and repair steps
- Shut off the power supply.
- Rotate the fan by hand and check that it turns easily.
- Check that the fan is properly wired and that all connections are secure.
- If the problem remains, replace the main PCB.
Models that show this code
4 models in D5FCFA
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: D5FCFAH service manual, p. 37. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.