Carrier · Heat pump

EC 07 Outdoor fan speed operating outside normal range

Medium severity D5FUHA

What the control is telling you

Outdoor fan speed stays too low or too high for a set time. The LED shows the failure code and the unit turns off. Same procedure as EH03. Recommended parts: connection wires, fan assembly, fan motor, PCB.

Applies to: D5FUHA

Likely causes

  • Outdoor fan blocked or binding
  • Fan wiring not correct or loose connections
  • Faulty outdoor fan motor
  • Faulty main PCB

Test and repair steps

  1. Shut off the power supply.
  2. Rotate the outdoor fan by hand and check that it turns easily.
  3. Check that the fan is wired correctly and connections are secure.
  4. If the problem remains, replace the main PCB.

Other codes on the same units

  • PC01 ODU voltage protection
  • PC02 Compressor top (or IPM) temp. protection
  • PC03 Pressure protection (low or high pressure)
  • PC04 Inverter compressor drive error
  • ---- Indoor units mode conflict
  • DF Defrost mode
  • EC 55 Quick maintenance code (outdoor)
  • EC 57 Quick maintenance code (outdoor)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: D5FUHA service manual, p. 25. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.