Carrier · Heat pump
4 Four flashes - speed limiting (25VNA8) / fan delay defeat on (24ANB/25HNB)
What the display is showing
Four flashes and a pause on the amber STATUS LED. On the Infinity 25VNA8/24VNA9 with a non-communicating thermostat it shows reduced capacity, with speed limited. On the 24ANB/25HNB heat pump it is also the indicator that the outdoor-fan delay after defrost has been defeated (fan starts immediately); it stays on while the forced defrost pins are shorted and for about 5 seconds after.
Applies to: Carrier Infinity 25VNA8/24VNA9 variable speed, 24ANB/25HNB two-stage and single-stage communicating outdoor units
What to do
- 24ANB/25HNB fan delay toggle with the unit on solid (standby), short the forced defrost pins for more than 15 seconds. The LED starts to flash 3 (delay active, 20 s) or 4 (delay defeated). The setting is remembered through power cycles; repeat the toggle to change it.
Models that show this code
15 models in Carrier Infinity 18VS 25VNA8, Carrier 2-stage 24ANB/25HNB
Other codes on the same units
- 1 Normal operation - 1 flash
- 1 long Capacity limited - one long flash
- 2 Normal operation - 2 flashes (high stage)
- 3 Three flashes - outdoor fan delay after defrost active (24ANB/25HNB)
- 5 Five flashes - brownout protection setting (24ANB/25HNB)
- 6 Six flashes - brownout protection setting (24ANB/25HNB)
- 16 Lost communication with user interface
- 25 Invalid model plug / inverter size
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier 25VNA8/24VNA9 service manual, Table 6 Fault Code Actions (status rows), p.15-16; Carrier residential A/C and heat pump service manual 24-25, Table 18 Troubleshooting (2-stage 24ANB/25HNB), p.60-61. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.