6 Six flashes - brownout protection setting (24ANB/25HNB)
What the display is showing
Six flashes and a pause on the amber STATUS LED report the state of the 230 V brownout protection after the installer toggles it (a last resort for very noisy power). The manual contradicts itself: Table 18 lists 5 flashes as protection disabled and 6 as active, while the written procedure says 5 = active (shipped state) and 6 = disabled. Confirm on the unit before relying on either reading. While the forced defrost short remains, OAT and OCT sensor faults are not cleared.
Applies to: Carrier 24ANB/25HNB two-stage units
What to do
- Brownout toggle (non-communicating) with power off, remove the OAT/OCT sensor connector and short the forced defrost pins, then power up.
- After about 3 seconds the setting toggles and the LED flashes the new state (5 or 6).
- Power down, refit the sensor connector and remove the short. Two toggles may be needed to reach the setting you want.
Models that show this code
8 models in Carrier 2-stage 24ANB/25HNB
Other codes on the same units
- 2 Normal operation - 2 flashes (high stage)
- 3 Three flashes - outdoor fan delay after defrost active (24ANB/25HNB)
- 4 Four flashes - speed limiting (25VNA8) / fan delay defeat on (24ANB/25HNB)
- 5 Five flashes - brownout protection setting (24ANB/25HNB)
- 16 Lost communication with user interface
- 25 Invalid model plug / inverter size
- 31 High pressure switch open
- 32 Low pressure trip
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier residential A/C and heat pump service manual 24-25, Table 18 (brownout rows) and 230 V Brown-Out Protection Defeated, p.59-61. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.