16 Lost communication with user interface
What the control is telling you
Amber STATUS light flashes 16: the outdoor board no longer hears the Infinity user interface.
Applies to: Carrier 25HNB6/25HNB9 two-stage HP; single-stage communicating HP
Likely causes
- Loose or broken ABCD wiring
- Wiring fault at indoor unit or UI
- UI or indoor unit without power
Test and repair steps
- Check the A, B, C, D connections at the UI, indoor unit and outdoor board.
- Confirm 24 V between C and D at the outdoor unit.
- Look at the green COMM LED it should be on steady once messages are received.
- After 2 min without messages the board returns to standby.
Models that show this code
8 models in Carrier 2-stage 24ANB/25HNB, Carrier single-stage communicating HP
Other codes on the same units
- 2 Normal operation - 2 flashes (high stage)
- 3 Three flashes - outdoor fan delay after defrost active (24ANB/25HNB)
- 4 Four flashes - speed limiting (25VNA8) / fan delay defeat on (24ANB/25HNB)
- 5 Five flashes - brownout protection setting (24ANB/25HNB)
- 6 Six flashes - brownout protection setting (24ANB/25HNB)
- 25 Invalid model plug / inverter size
- 31 High pressure switch open
- 32 Low pressure trip
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier Residential AC & HP Application Guideline and Service Manual 24-25-9SM (text export), Table 14 Status Codes / Table 18 Troubleshooting. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.