Trane · Air handler · Startup

Modular blower run test mode

P0V0 modular blower

What happens, in order

  1. Scroll to run with the Menu key, then press the Option key; the display counts down and the test starts
  2. The test takes about 70 seconds to begin
  3. Blower runs on first-stage compressor speed for 30 seconds
  4. Blower then runs on second-stage compressor speed for 30 seconds
  5. The pattern repeats two more times unless the test is exited
  6. The outdoor unit does not run in this test; it is only for checking each mode of the blower
  7. The Option key can hold a step while measurements are taken
  8. Exit by pressing Menu, cycling power to the blower, or making a valid call for capacity or fan

Timings and thresholds

ItemValue
Time to startabout 70 s
Each blower step30 s
Repeats3 passes in all

Applies to: P0V0 modular blowers

Models

P0V0A000M30SCAP0V0B000M40SCAP0V0C000M50SCAP0V0D000M50SCA

More Trane air handler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane P0V0 modular blower installation 18-GE20D1-1E-EN (Nov 2021), Sequence of Operation pp.30-33. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.