Trane · Air handler · Cooling

Modular blower cooling call (single and two-stage)

P0V0 modular blower

What happens, in order

  1. Thermostat closes R-Y1-G, sending 24 V to Y1 and G on the blower control; expect 24 V between Y1 and B/C and between G and B/C
  2. 24 V goes to the outdoor unit through the thermostat wiring and starts the first-stage compressor
  3. Indoor blower ramps to first-stage cooling airflow; the display alternates CL1 and ARF (calculated airflow, shown value times 10)
  4. The factory Y1-O jumper must stay in place for the CL1 readout; with it removed the display shows HP1
  5. Second stage R-Y2 closes, 24 V reaches Y2, the outdoor unit goes to second stage and the blower ramps to second-stage airflow (display CL2)
  6. Satisfied contacts open, the outdoor unit stops and the blower stops, unless a blower off delay is enabled in the menu (display returns to IDL)
  7. First-stage airflow is set from the ODU menu: 80 percent for 2-stage with one compressor, 50 percent for 2 compressors

Timings and thresholds

ItemValue
Airflow displayvalue x 10 (080 = 800 cfm)
Calculated airflow settle timeabout 1 to 2 min
First-stage airflow, 1 compressor80 percent
First-stage airflow, 2 compressors50 percent

Codes you may see during this

CL1, CL2, IDL, ARF; blower faults e01, e6.1, e6.2, e12 to e18 on the display

Applies to: P0V0 modular blowers on air conditioning

Models

P0V0A000M30SCAP0V0B000M40SCAP0V0C000M50SCAP0V0D000M50SCA

More Trane air handler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane P0V0 modular blower installation 18-GE20D1-1E-EN (Nov 2021), Sequence of Operation pp.30-33. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.