Trane · Air conditioner · Cooling

Cooling sequence

XR302XR303

What happens, in order

  1. Press SYSTEM to select Cool.
  2. Set setpoint below room temperature; blower starts on high speed immediately, then cold air.
  3. If setpoint flashes, the compressor lockout is active.
  4. Lower setpoint 3° below room; second stage cooling starts and display shows 'System On +2'.
  5. Raise setpoint above room to stop cooling.

Timings and thresholds

ItemValue
Compressor lockout (CL)5 minutes between cooling cycles
Fan delay on compressor start (CO on)5 seconds
Fan run after compressor off (CO on)20 seconds
Cool Savings first 1° offset1 hour continuous run
Cool Savings each additional 1°every 30 minutes of run

Codes you may see during this

System On; System On +2; Flashing setpoint; Cool Savings

Applies to: Cooling and heat pump cooling

Models

TCONT302TCONT303

More Trane air conditioner sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane XR302/XR303 installation and user guide, p. 19-20 and 16. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.