Trane · Air conditioner · Cooling
Cooling efficiency booster (single stage compressor)
What happens, in order
- With BK output enabled and installer step 40 on, indoor airflow drops during cooling.
- This applies when the outdoor temperature is below the set point.
- The outdoor temperature sensor must be installed and enabled in installer step 10.
Timings and thresholds
| Item | Value |
|---|---|
| Indoor airflow during booster | 80% |
| Outdoor temperature below | 87 F |
Applies to: Single stage compressor with BK output enabled
More Trane air conditioner sequences
- Cooling droop cycling · Cooling
- Cooling sequence · Cooling
Related
Trane error codes · Trane tips · Trane parts · All Trane sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Trane XR402 installer's guide 18-HD29D3-4, p. 15. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.