Trane · Air conditioner · Cooling
Cooling droop cycling
What happens, in order
- When room temperature is at or below the cooling setpoint, the compressor cycles on to remove moisture.
- The control holds the room 1 or 2 degrees below the cooling setpoint.
- Droop ends when the room temperature rises back above the cooling setpoint.
- With BK output enabled, airflow drops to 80% during droop.
Timings and thresholds
| Item | Value |
|---|---|
| Airflow during cooling droop (BK enabled) | 80% |
Applies to: XR402 cooling with cooling droop set to 1 or 2 degrees
More Trane air conditioner sequences
- Cooling efficiency booster (single stage compressor) · Cooling
- Cooling sequence · Cooling
Related
Trane error codes · Trane tips · Trane parts · All Trane sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Trane XR402 installer's guide 18-HD29D3-4, p. 15. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.