Midea · Furnace · Other

Refrigerant leak sensor response (A2L coil)

A2L 96 percent two-stage (BGH96M)

What happens, in order

  1. Refrigerant sensor wired to CN30 and drive board switch SW1-2 set ON
  2. Sensor communication lost for 2 minutes LED2 flashes green once, Y signal is cut and cooling stops
  3. Refrigerant above the alarm limit LED2 flashes green twice, Y is cut, cooling stops and the furnace blower keeps running until the concentration drops to a safe level
  4. Sensor wired but SW1-2 left OFF LED2 flashes green three times; set SW1-2 to ON
  5. Sensor expired or faulty LED2 flashes green four times, Y is cut and cooling stops; a new sensor is needed

Codes you may see during this

LED2 1 2 3 4 green flashes

Applies to: Midea A2L 96 percent gas furnace paired with an A2L coil

Models

BGH96M series

More Midea furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Midea A2L 96 percent gas furnace troubleshooting guide, A3 Requirements for refrigerant leakage sensors. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.