Midea · Furnace · Ignition
Failed ignition and re-ignition
What happens, in order
- W1 call inducer on high for 15 s, then low speed
- Igniter preheats for 17 s, valve opens, igniter turns off after 3 s
- No flame valve stays open only 4 s
- Inducer runs on high for 60 s
- Low pressure switch is tested again
- Igniter preheats for 27 s
- Valve opens again and igniter turns off after 3 s
- After two failed attempts the system locks out (E7)
- Lockout clears itself after 1 hour, or by cutting 115 V for 1 to 20 s, or by dropping the thermostat call for 1 to 20 s
Timings and thresholds
| Item | Value |
|---|---|
| First preheat | 17 s |
| Gas on with no flame | 4 s |
| Inducer high between tries | 60 s |
| Second preheat | 27 s |
| Lockout auto reset | 1 hour |
Codes you may see during this
E7 E8
Applies to: Midea A2L 96 percent gas furnace
Models
BGH96M060B3ABGH96M080B3ABGH96M080C4ABGH96M100C5ABGH96M100D5ABGH96M120D5A
More Midea furnace sequences
- Low fire heat call (W1 only) · Ignition
- High fire heat call (W1 + W2) · Heating
- Refrigerant leak sensor response (A2L coil) · Other
Related
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Midea A2L 96 percent gas furnace troubleshooting guide, Appendix A2 and section 2.2. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.