Midea · Furnace · Ignition

Failed ignition and re-ignition

A2L 96 percent two-stage (BGH96M)

What happens, in order

  1. W1 call inducer on high for 15 s, then low speed
  2. Igniter preheats for 17 s, valve opens, igniter turns off after 3 s
  3. No flame valve stays open only 4 s
  4. Inducer runs on high for 60 s
  5. Low pressure switch is tested again
  6. Igniter preheats for 27 s
  7. Valve opens again and igniter turns off after 3 s
  8. After two failed attempts the system locks out (E7)
  9. Lockout clears itself after 1 hour, or by cutting 115 V for 1 to 20 s, or by dropping the thermostat call for 1 to 20 s

Timings and thresholds

ItemValue
First preheat17 s
Gas on with no flame4 s
Inducer high between tries60 s
Second preheat27 s
Lockout auto reset1 hour

Codes you may see during this

E7 E8

Applies to: Midea A2L 96 percent gas furnace

Models

BGH96M060B3ABGH96M080B3ABGH96M080C4ABGH96M100C5ABGH96M100D5ABGH96M120D5A

More Midea furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Midea A2L 96 percent gas furnace troubleshooting guide, Appendix A2 and section 2.2. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.