Midea · Furnace · Heating
High fire heat call (W1 + W2)
What happens, in order
- Call for heat; inducer on high speed, low pressure switch closes
- Inducer to low speed; igniter preheats
- Gas valve opens, burners light, igniter off after 3 s
- 5 s delay before gas valve, inducer and pressure switch go to the high stage
- 30 s later the blower motor starts
- Running on high stage
- Call ends inducer shuts down after a 15 s delay
- Blower runs at high speed for 30 s
- Fan delay then runs the time set by S1-3 and S1-4 (default 180 s)
Timings and thresholds
| Item | Value |
|---|---|
| Inducer high / switch proving | 15 s |
| Igniter preheat | 17 s |
| Delay to high stage | 5 s |
| Blower on delay | 30 s |
| Inducer stop delay after call ends | 15 s |
| Blower high speed after call ends | 30 s |
| Fan off delay (default) | 180 s |
Codes you may see during this
E3
Applies to: Midea A2L 96 percent gas furnace
Models
BGH96M060B3ABGH96M080B3ABGH96M080C4ABGH96M100C5ABGH96M100D5ABGH96M120D5A
More Midea furnace sequences
- Failed ignition and re-ignition · Ignition
- Low fire heat call (W1 only) · Ignition
- Refrigerant leak sensor response (A2L coil) · Other
Related
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Midea A2L 96 percent gas furnace troubleshooting guide, Appendix A1.2. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.