Midea · Furnace · Ignition

Low fire heat call (W1 only)

A2L 96 percent two-stage (BGH96M)

What happens, in order

  1. W1 calls; inducer starts on high speed and the low pressure switch closes
  2. Inducer drops to low speed and the igniter energizes for preheat
  3. Gas valve opens and the burners light; igniter turns off 3 s later
  4. Blower motor starts after a 30 s delay
  5. System runs on low fire
  6. Call ends and flame is gone post-purge starts
  7. Fan delay clears remaining heat; time set by dip switches S1-3 and S1-4

Timings and thresholds

ItemValue
Inducer high speed / switch proving15 s
Igniter preheat17 s
Igniter off after valve opens3 s
Blower on delay30 s
Post-purge15 s
Heat fan off delay (default)180 s

Codes you may see during this

E1 E2 E3 E4 E5 E6 E7 E8 FL Pr

Applies to: Midea A2L 96 percent gas furnace

Models

BGH96M060B3ABGH96M080B3ABGH96M080C4ABGH96M100C5ABGH96M100D5ABGH96M120D5A

More Midea furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Midea A2L 96 percent gas furnace troubleshooting guide, Appendix A1.1. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.