FlowMax · Boiler · Startup

Switch-on and mode selection

FLOWMAX 90/120

What happens, in order

  1. Open the gas isolation valve under the unit
  2. Set the ON/OFF switch to ON
  3. Check the display for flashing codes; H2O means no water or low pressure, fill the system to at least 1 bar and it restarts by itself
  4. In WINTER mode with a room thermostat connected, the unit lights automatically on a heating call
  5. SUMMER mode heating circuit locked out, burner lights only for a domestic hot water call; symbol flashes while burning
  6. WINTER mode burner lights only for a heating call (domestic hot water off)
  7. SUMMER/WINTER mode burner lights for either heating or DHW calls
  8. If a fault stops the unit and it will not restart, unplug for 30 seconds, plug in and try the ON/OFF switch again

Timings and thresholds

ItemValue
Heating temperature range30-80 C (low temp 25-59 C)
DHW temperature range35-60 C
Minimum system pressure1 bar
Power reset wait30 s

Codes you may see during this

H2O E01

Applies to: FLOWMAX-90, FLOWMAX-120

Models

FLOWMAX-90FLOWMAX-120

More FlowMax boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: FLOWMAX-90 user manual (control panel, start-up, diagnostics). Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.