FlowMax · Boiler · Domestic hot water

DHW call with pump overrun and priority

FLOWMAX 90/120

What happens, in order

  1. Hot water draw or storage cylinder call starts the DHW mode (3-way valve moves to DHW)
  2. Burner modulates to the DHW setpoint
  3. When the call ends the burner stops and the circulation pump runs on for the DHW overrun time
  4. DHW priority function (parameter 13) adds a 2 minute delay on the DHW function when switched on

Timings and thresholds

ItemValue
DHW pump overrun (param 8)00-90 steps of 5 s, default 18 = 90 s
DHW priority delay (param 13)2 min when enabled
DHW setpoint range95-140 F, or 95-160 F with the higher setting

Codes you may see during this

E06 E12

Applies to: FLOWMAX-120

Models

FLOWMAX-120

More FlowMax boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: FLOWMAX-120 installation manual (DIGITECH PCB SM20021, parameters 4-8, function codes 07/08/28). Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.