Carrier · Heat pump · Other

Variable-speed unit: high pressure switch protection and lockout

Infinity 25VNA824VNA9

What happens, in order

  1. High pressure switch opens (opens about 600 psig, closes about 470 psig at 77 F) and code 31 is shown
  2. After 6 minutes, if there is still a call and the switch has reset, the PEV opens for 150 s to equalize pressure
  3. Compressor and fan then restart one stage lower and keep stepping down if the switch trips again
  4. The step-down and return to top stage clear after 2 hours of running with no more trips
  5. If it trips again at the lowest stage the fault is raised to code 84 (high pressure lockout); from stage 5 this takes five trips in a row, from stage 1 just one

Timings and thresholds

ItemValue
Retry delay6 min
PEV equalize150 s
Reset of step-down2 h accumulated run without trips
HPS opens600 psig
HPS closes470 psig

Codes you may see during this

31 84

Applies to: Carrier Infinity 25VNA8 variable-speed heat pump and 24VNA9 variable-speed air conditioner

Models

25VNA824VNA9

More Carrier heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier Infinity 25VNA8/24VNA9 variable-speed heat pump and A/C service manual, Time Delays, Defrost, High and Low Pressure Protection. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.