Carrier · Heat pump · Cooling

Non-communicating heat pump: cooling with 5-minute compressor delay (HK32EA003/008)

Performance

What happens, in order

  1. Control powers up (24 V between R and C) and a 5-minute timer starts; compressor will not start until it expires
  2. Thermostat makes R-O, R-Y and R-G on a call for cooling
  3. R-O shifts the reversing valve to cooling
  4. R-Y feeds the safeties and energizes terminal T1 on the board
  5. If the compressor has been off 5 min (or power was off 5 min), fan relay OF2 and T2 energize, closing the contactor to start outdoor fan and compressor
  6. Thermostat satisfied R-Y drops, compressor and fan stop, and the 5-minute timer restarts
  7. With Carrier thermostats the reversing valve stays in cooling position until the thermostat goes to heat or off

Timings and thresholds

ItemValue
Compressor time delay5 min

Applies to: Carrier / Bryant / Payne split heat pumps with HK32EA defrost control boards (Performance Series and Comfort Series)

Models

HK32EA003HK32EA008

More Carrier heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier-Bryant residential A/C + HP Application Guideline and Service Manual (R-410A, 24-25), System Function and Sequence of Operation, Defrost Control. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.